HT2XAS0D | RH/T Deluxe | 2% | Analog | 10K T2 | Veris (OBSOLETE)
Overview
Details for HT2XAS0D
RH/T Deluxe | 2% | Analog | 10K T2
Description
All HT/HWS Series institutional grade relative humidity transmitters are designed to meet the rigorous needs of pharmaceutical labs, hospitals, science labs, and other settings that call for precise environmental control. Internal jumpers control access to a feature that allows adjustment of the calibration offsets. The devices can also be made tamper resistant using a jumper to disable keypad programing functions. HT/ HWS models are calibrated with NIST traceable calibration equipment.
Analog Output Transmitter Analog output models feature a keypad to make adjusting humidity and temperature setpoint values easy. They transmit the setpoint values back to a control system by means of dual outputs. A slide-switch allows easy selection of output type, either 4-20mA or 0-5V/0-10VDC signals. Dual outputs enable effortless control of both humidity and temperature in a single, compact sensor.
Setpoint Relay Transmitter The HT Series setpoint relay models also offer thermostat or humidistat functionality. Two separate relays can be configured to control heating and cooling when in thermostat mode, or humidifying and de-humidifying when in humidistat mode. HWS models offer the same precise humidity measurement and control as the HT, but without the temperature and thermostat features.
Features
- Independent RH and T (HT relay) or analog setpoint outputs (HT analog) provide application flexibility
- LCD for local display of readings and setup values
- Offset function adjusts calibration intervals for both RH and T (HT models)
- Switch-selectable 4-20mA or 0-10V/0-5VDC analog outputs
- Multi-point calibration to 1% RH, traceable to NIST
- Replaceable RH sensor element supports field calibration offset saves time
- Semiconductor temperature sensor can be field calibrated
Application
- Hospitals and operating rooms, pharmaceutical labs
- Clean rooms
- Food processing plants
- Environmental testing facilities, & other institutional applications
Specifications
Input Power Class 2; 15 to 30VDC or 24VAC 50/60Hz, 100mA max.
Outputs, Analog Switch-selectable 4-20mA, or 0-10V/0-5VDC (switch affects both outputs)
Outputs, Relay (Relay models only) 2 Form C (SPDT), 1A 30VDC, resistive, 30W max.
RH Sensor Digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138*
Accuracy at 25°C from 10-80% RH** (Multi-point calibration NIST traceable)
±2%, 3%, or 5% models; ±1% at 20-50% RH on HTA models ±1% at 12-40% RH on HTR models in mA output mode; ±1% at 30% RH on HTR models in voltage output mode
Reset Rate*** 24 hours
Stability ±1% @ 20°C (68°F) annually, for two years
Hysteresis RH: 1.5% (typical), Temp: 1° to 10°F in 1°F increments
Linearity Included in accuracy spec.
Operating Humidity Range 0-100% RH non-condensing
Temperature Coefficient ±0.1%RH/°C above or below 25°C (typical)
Operating Temperature Range 10° to 35°C (50° to 95°F)
Temperature Accuracy ±1.0°C (±1.8°F)
Physical UL 94V-0 fire retardant ABS
Scaling RH: 0-100%; Temp: 10°to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F) menu selectable
Calibration Offset RH: Adjustable ±10% in 0.1% increments; Temp: Adjustable ±10° in 0.1° increments
Setpoint Range RH: 10-80% in 1% increments; Temp: minimum to full scale in 1°F increments
Specifications
Item Number | HT2XAS0D |
Brand | Veris |