Pwr Mtr | DIN | LON | 1Pulse&Alarm | For U018CTs
The E50FxA DIN rail power meter provides a solution for measuring energy data with a single device. Inputs include pulse, control power, CT and 3-phase voltage. The E50FxA supports multiple output options, including solid state phase loss alarm relay contacts (E50F2A only), LON. The LCD screen on the faceplate allows instant output viewing. These meters include built-in CT integrators and CT power supplies. The E50F2A work only with Veris E683 series rope style CTs. The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022. The E50 can be mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a panel. The meter is not sensitive to CT orientation to reduce installation errors.
- Alarm output (normally close)
- 1 pulse input (normally open): solid-state or mechanical contacts (current less than 1 mA)
- Communication port: 2-wire, LON TP/FT-10 output
- Mounting location - not suitable for wet locations, for indoor use only
Specifications
Item Number | E50F2A |
Brand | Veris |
Accuracy | +/- 0.2% |
Communication | LON |
Dimensions | 3.6" (91 mm) W x 4.2" (107 mm) W x 2.3" (59 mm) H |
Display Type | LCD |
Environmental Conditions | Humidity Range: Less Than 95% RH Non-Condensing; Storage Temperature: -40 to 158 °F; Altitude of Operation: 3000 m |
Frequency Rating | 50 - 60 Hz |
Metering Product Family | E50 Power Meter |
Monitored Voltage Range | 90 - 600 VAC |
Mounting | Din-Rail |
Operating Temperature | -22 - 158 °F |
Output Specifications | Alarm: 30 VAC/VDC; 100 mA Maximum (NC); LON |
Power Monitoring | E5x Series Power and Energy Meters |
Product Type | Compact Power and Energy Meter with LON TP/FT-10 Communication |
Range | E50 |